Single- vs Double-Jacket ADSS, and PE vs AT Sheath

Most ADSS specifications go wrong in one place. The tender carries a single line — "double jacket, AT sheath" — and nobody in the review can say which line condition produced it. Jacket count and sheath compound are two separate decisions: one mechanical, driven by the span schedule; one electrical, driven by the field at the attachment point.

This page separates them, for the stage where ADSS has already been chosen over OPGW and the specification still has to name the construction. It replaces no sag-and-tension review and publishes no company-wide span cut-off or kV rating for a sheath type.

The short answer

DecisionDriven byUsual starting pointConfirm before the specification is frozen
Jacket count: single or doubleSpan schedule, wind and ice loading, sag and tension designSingle jacket for shorter, lightly loaded spans; double jacket for longer spans, heavier loading, or the catalog long-span rangeSag-and-tension calculation for the actual spans; datasheet for the offered fiber count
Sheath compound: PE, AT, or LSZHElectrical environment at the attachment point, plus fire requirements in closed sectionsPE in low-stress positions; AT where tracking resistance is required; LSZH in tunnels and building entriesSpace potential at the intended clamp position, from the line designer; the supplier's sheath rating

Two points sit behind that table. A catalog span label is an entry point for the order, not a design approval, and the sheath compound comes from the electrical environment at the clamp, not the line label. Ebocom publishes neither a span cut-off nor a space-potential figure, so both are confirmed per project.

What is the difference between single-jacket and double-jacket ADSS?

Single-jacket ADSS places the aramid yarn and a single outer sheath over the cable core. Double-jacket ADSS adds an inner sheath, so the yarn and the outer sheath sit over a sheathed core. The extra jacket is a construction choice for higher mechanical demand — longer spans, heavier wind or ice, or a route that needs more crush and handling margin — not a fiber-count upgrade. Catalog span labels are starting points only. The approved design still has to come from the route's span schedule, sag limits and wind-and-ice loading, with a project-specific datasheet.

Single-jacket vs double-jacket: a construction choice

Single-jacket ADSS is the shorter layer stack: core, aramid yarn, outer sheath. The yarn carries the tensile load; the sheath protects both.

Double-jacket ADSS inserts an inner sheath between the core and the strength members. It gives the aramid a round bed so the yarn layer stays even along the span, adds a second barrier in front of the fiber core, and adds margin for handling and crush. It also adds weight and diameter for the same fiber count, which changes drum lengths and the hardware envelope. Moving a project from single to double jacket "for safety" is a mechanical change to be checked against tower loading, not a free upgrade.

What the Ebocom catalog already lists

The ADSS catalog carries both constructions, and the published span wording differs from page to page. Read those figures as entry points, not policy.

  • Single jacket, 12–96 core, 100M title. The single-jacket 100M page has a spec table listing 2–144 core, a span range from 50 m to 500 m+, and HDPE or LSZH jacket. Title, slug and table disagree.
  • Single jacket, 72 core, 100M. The 72-core single-jacket page lists HDPE or AT jacket, a typical span of 50–150 m, and G.652.D fiber — the clearest evidence here that sheath material and jacket count are separate choices.
  • Double jacket, 24, 48 and 96 core, 200M. The 24-core, 48-core and 96-core pages state an installation span up to 200 m with a dual PE jacket. The 72-core double-jacket page states 100–800 m — not the same range.
  • Long span, 24–96 core. The long-span ADSS page states a design span of 400–600 m with a dual PE jacket, or AT for routes with a high induced field, with G.652D, G.657A1 or G.657A2 fiber.
  • High fiber count. The 288-core page lists HDPE, or AT for routes with a high induced field, span set by route design. The 144-core page leaves most parameters to be confirmed; nothing should be borrowed from a neighboring page.
  • LSZH. The LSZH ADSS page covers 24–96 core in single or double jacket, span set by route design.

PE vs AT sheath: choose by the electrical environment, not the line-voltage label

The sheath is not only a weather jacket. It is also an insulating surface sitting in the field of the phase conductors. Under wet and polluted conditions a conductive film can form on it; current flows along that film, dries it in narrow bands, and the dry bands take the voltage. Small arcs bridge them, erode and carbonize the surface, and can track through the jacket to the core.

That is dry-band arcing, and it is why an anti-tracking sheath exists. AT is a track-resistant compound: the polymer and its additive package resist surface erosion and carbon formation. It is not PE made thicker — a thicker jacket resists mechanical damage, not electrical tracking.

The quantity that predicts the risk is the space potential: the potential at the cable surface where it is clamped. It depends on line voltage, phase arrangement, tower geometry, attachment height and distance to the nearest conductor. It is a design output, not a label printed on the line.

Published application guidance puts numbers on this, and those numbers need care. Manufacturer installation instructions for ADSS, for example Prysmian's, describe a standard sheath as compatible with space potential up to 12 kV in low-pollution areas and a tracking-resistant sheath up to 25 kV, and advise calculating space potential above 69 kV. Corning's application note on optical cables near high-voltage circuits summarizes IEEE 1222 as two categories: sheath potential not exceeding 12 kV, and above 12 kV.

Both are external references: the suppliers' published application values and their reading of the standard. They are not Ebocom ratings, not clauses quoted from the paid text of IEEE 1222, and they do not transfer to another manufacturer's cable. Ebocom's own space-potential values are confirmed per project.

The standards themselves: IEEE 1222-2019 covers testing and performance of ADSS cable on power lines; IEC 60794-4-20:2018 is the family specification for aerial cables along power lines. Both describe how ADSS is tested; neither selects a sheath for a clamp position.

When should I specify an AT sheath instead of PE?

Specify the sheath from the electrical environment at the attachment point, not from the line-voltage label alone. A polyethylene (PE) sheath is the usual starting point in a low electrical-stress position. An anti-tracking (AT) sheath is a track-resistant compound intended to resist dry-band arcing where the cable sits in a stronger field, typically in wet or polluted conditions. Industry application guides often discuss this in terms of space potential and cite IEEE 1222 when classifying the electrical environment; published 12 kV / 25 kV figures belong to those references and to other manufacturers' ratings unless a supplier states its own values. Ask the line designer and the cable supplier to confirm the sheath against the intended clamp position. Do not transfer another manufacturer's rating to a different cable.

Why "110 kV so AT" is not a calculation

Two lines at the same nominal voltage can put the cable in different fields. A compact tower with close phase spacing and a high attachment point is not the environment of a wide tower where the cable hangs well below the conductors, even when both are called 110 kV — and the same holds at 220 kV. The voltage class sets the order of magnitude; the geometry sets the number at the clamp.

ADSS is normally hung below the phase conductors, which is why the attachment point matters more than the line label; see the ADSS vs OPGW selection guide for that geometry. When the space potential is not available, do not invent one from the voltage class, and do not accept a quotation that quietly did.

Treat jacket count and sheath compound as two decisions

Once the axes are separate, the combinations stop looking strange.

ConstructionTypical reason for the requestStill to be checked
Single jacket, PEShort, lightly loaded span in a low-stress electrical positionSpan and tension design; space potential at the clamp
Single jacket, ATShort span, but the clamp is in a stronger field or the route is polluted and wetWhether single-jacket mechanical margin covers the span
Double jacket, PE on both layersLonger or more heavily loaded span in a low-stress positionWeight, diameter, hardware envelope, drum plan
Double jacket, AT outer sheathLonger span plus a stronger electrical environmentThat the inner construction and the AT outer layer are both on the drawing
LSZH, single or double jacketFire, smoke or toxicity requirement in a tunnel, station or building entryWhich fire standard applies, and whether the span works with that construction

Two rules keep the table honest. The rows are not a price or availability list: each combination's catalog entry point is confirmed per project, and the drawing has to show the layer stack ordered. And AT does not automatically mean double jacket — Ebocom publishes a single-jacket page offering AT and a long-span page offering either dual PE or AT, so that assumption should be confirmed, not specified as fact.

LSZH is a fire-and-smoke decision, not an electrical one. It comes on single-jacket or double-jacket ADSS, so it does not replace the jacket-count decision and is no substitute for AT where tracking resistance is the requirement. Where a closed section and a high-field section sit on one route, state both.

Can I choose the ADSS jacket from the line voltage or a single span figure?

No. Jacket count and sheath compound are two separate decisions, and neither is settled by writing "110 kV" or "200 m span" alone. Two lines with the same nominal voltage can produce different fields at the clamp, depending on tower geometry and attachment position. Likewise, a catalog span label does not replace wind, ice, sag and hardware review. Put the span schedule, the intended attachment points and the required sheath or "please recommend from the electrical environment" in the RFQ, and use a project-specific sag-and-tension review before the specification is frozen.

When ADSS sheath choice is not the main decision

  • The route needs a ground wire, fault-current path or lightning protection. That is an OPGW discussion: compare the two families in the ADSS vs OPGW selection guide before returning to sheath selection.
  • The span is short and outside a significant field, for example a pole-to-building drop. A construction such as ASU cable may be simpler and needs no ADSS sheath decision.
  • The space potential at the attachment point is too high for the chosen sheath. The productive discussion is then about the attachment point, the tower position or the route, not a heavier sheath. Acceptable positions are set by the line design and the supplier's sheath rating.

One limit belongs in the review even though it is not a sheath property. All-dielectric describes the construction; it does not authorize work on or near energized conductors. Clearance and work method belong to the line owner and local rules.

What to put in the RFQ so quotes are comparable

This page adds the sheath block; the rest of the field list belongs to the ADSS span and RFQ checklist, which covers sag, hardware, drum lengths and route data. Add to it:

  • The span schedule, including the longest crossing and the controlling span, plus wind and ice loading in the units and return period the project uses.
  • The intended attachment point on each structure type, located precisely enough to find on the tower drawing.
  • The line arrangement and nominal voltage, marked as input to the space-potential calculation rather than as the basis for sheath selection.
  • The required sheath compound (PE, AT or LSZH) or the explicit request "recommend the sheath from the space potential at the stated attachment point", and the same for jacket count: single or double, or "recommend from the tension design".
  • Pollution and wetting conditions, if the line owner has them, plus any fire performance requirement for tunnels, stations or building entries.

Ask each supplier to answer in the same terms: the sheath offered and its basis at the stated attachment point; the drawing for the offered fiber count, showing the inner sheath where a double jacket is offered; and datasheet values with test conditions. A quotation that names a sheath without naming the attachment point it was selected for is not comparable with one that does.

Request a quote

When the span schedule, the attachment points and the sheath requirements are ready, send the project details to Ebocom. Include the line arrangement and voltage as inputs to the calculation, and state whether the sheath is fixed or a recommendation is wanted from space potential.

Ask for the construction drawing and datasheet that match the requested fiber count and the actual spans. For a double-jacket offer, ask for the layer stack in writing; for an AT offer, ask which attachment position the recommendation is based on.